Bell & Gossett Circuit Sensor® Flow Meter, Type A, 47 to 140 gpm, 300 psig, 3 in, +/- 1 % Accuracy, 250 deg F, Cast Iron, 5-13/16 in W x 1-1/2 in D
The Bell & Gossett Circuit Setter® Flow Meter is a precision machined wafer-type orifice insert that is installed between standard 125, 150, 250 or 300 psi ANSI flanges, to monitor system flow with a minimum friction head loss. System flow is determined by obtaining a differential pressure across the flow meter orifice by sensing upstream and downstream pressures through the readout valves, then referring to the calibrated nameplate for the corresponding flow. Circuit Sensor® Flow Meters are suitable for a maximum operating temperature of 250 deg F (121 deg C), and are equipped with RV-125A Readout Valves fitted with an integral EPT check valve designed to minimize system fluid loss during the monitoring process.
ANSI Specified
Accuracy
+/- 1 %
Connection Size
3 in
Dimensions
5-13/16 in W x 1-1/2 in D
Flow Rate
47 to 140 gpm
Material
Cast Iron
Pressure Rating
300 psig
Temperature Rating
250 deg F
Type
Type A
Brand
Bell & Gossett
Readout valves - brass with integral EPT check valve